Kitchen exhaust calculator: airflow, make-up air and budget
Choose the hood and the cooking line, enter the dining room. You get exhaust and make-up air in m³/h, cooling capacity, a power estimate and an indicative budget, and can send it to our engineer on WhatsApp.
- Hood airflow from the International Mechanical Code 2021
- Local make-up air up to 60 %, transfer air from 40 %
- Cooling from diners, lighting, envelope and outdoor air
- Result goes to WhatsApp with one tap
How the calculator works
Exhaust. The hood airflow is the hood length multiplied by the minimum rate per metre from the International Mechanical Code table, which depends on the hood type and the cooking duty. Charcoal and wood fires (extra-heavy duty) are not allowed under back-shelf hoods.
Replacement air. The air a hood removes has to come back. We supply up to 60 % of it as local make-up air in the kitchen and bring at least 40 % from the dining room as transfer air. This split follows the design guide of the Food Service Technology Center, which warns that pushing most of the replacement air through the hood area disturbs capture. The small imbalance also keeps smells on the kitchen side; see kitchen air balance.
Cooling. The dining room must receive at least the outdoor air of ASHRAE 62.1 for restaurant dining (3.8 L/s per person plus 0.9 L/s per m²), and never less than the transfer air it passes to the kitchen; the larger of the two is cooled from Bali design conditions (ASHRAE 2021, Ngurah Rai: 32.5 °C dry bulb, 26.6 °C wet bulb) to 24 °C and 55 %, an enthalpy difference of 32.7 kJ/kg. Diners are counted at 160 W each including food, lighting at 10 W/m²; envelope and sun are an assumption, 40-65 W/m² for a shaded room and 65-90 W/m² for large glazing. One PK is taken as 2.64 kW (9,000 BTU/h).
Power. Air conditioning at an efficiency (EER) of 3.0 W/W, in line with the Indonesian minimum of 2.9 W/W; fans at 2.0 kW per m³/s of air; lighting and sockets at 20 W/m²; electric cooking equipment at a demand factor of 0.7; power factor 0.9 and 25 % spare capacity. The result is rounded up to the next three-phase capacity (breaker rating × 3 × 220 V: 23, 33, 41.5, 53, 66 kVA and so on). Above 197 kVA the connection moves to medium voltage.
Budget. Our indicative Bali ranges from the pricing page: exhaust by hood length, air conditioning per PK (cassette), electrical and Revit design per m², grease trap by seats. Plumbing, water treatment and finishes are quoted after the survey.
The calculator gives a first estimate for a typical restaurant. Long duct routes, several hoods, open-air dining or unusual equipment change the numbers; that is what the free survey is for.
- International Mechanical Code 2021, 507.5 Capacity of hoods (UpCodes)
- CEC / FSTC: CKV Design Guide 2, Optimizing makeup air (2004)
- ASHRAE 62.1-2016 addendum: minimum ventilation rates
- ASHRAE 2021 climatic design conditions, Ngurah Rai (ashrae-meteo.info)
- Engineering ToolBox: heat gain from persons
- Permen ESDM 57/2017: air conditioner energy labels
- AIVC Technical Note 65: specific fan power
- PLN tariff adjustment, Q3 2026
Questions owners ask us
Why does hood type change the airflow so much?
An island hood is open on all sides, so room air currents reach the plume from every direction; it needs more airflow per metre than a wall hood for the same cooking.
What if I do not know the cooking duty?
Take the heaviest appliance under the hood: one charbroiler makes the whole hood heavy duty.
Is the budget a quote?
No. It is an indicative range for a first conversation; the quote follows the survey and the design.
Can I send the result to you?
Yes, the green button sends all inputs and results to our engineer on WhatsApp.